West Virginia design temperatures

Outdoor heating and cooling design conditions for 7 West Virginia weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for West Virginia weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Beckley MemorialWMO 724120 · 1973–19962,513 ft3 °F8 °F82 / 69 °F85 / 70 °FLoad calculator
Bluefield/MercerWMO 724125 · 1973–19962,858 ft4 °F9 °F82 / 69 °F84 / 69 °FLoad calculator
Charleston/KanawhaWMO 724140 · 1973–1996981 ft5 °F11 °F89 / 73 °F91 / 74 °FLoad calculator
Huntington/Tri StateWMO 724250 · 1973–1996837 ft6 °F12 °F89 / 74 °F92 / 75 °FLoad calculator
MartinsburgWMO 724177 · 1973–1996558 ft8 °F13 °F91 / 74 °F93 / 74 °FLoad calculator
Morgantown/HartWMO 724176 · 1973–19961,247 ft4 °F9 °F87 / 72 °F89 / 73 °FLoad calculator
Wheeling/OhioWMO 724275 · 1973–19961,198 ft1 °F7 °F88 / 73 °F90 / 74 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states