Building Heat Loss Calculator

Add up the heat a building loses through each wall, window, door, ceiling and floor, plus air leakage, at your design temperatures — the classic component method.

Method reviewed October 25, 2026. Version 1.0.0. How it works

Your inputs

Unit system

Including air films. U = 1 ÷ R.

Including air films. U = 1 ÷ R.

Including air films. U = 1 ÷ R.

From a blower-door test or an estimate; 0 to leave out air leakage.

Result

Total heat loss
81,639BTU/h
Total heat loss
23.93kW

Total heat loss about 81,639 BTU/h (23.9 kW) at 46 °F temperature difference.

Conduction (all components)
61,767BTU/h
Air leakage
19,872BTU/h
UA (conduction per °F)
1,343BTU/h·°F

Heat loss by component

1. Wall
22,978BTU/h
2. Window
20,240BTU/h
3. Ceiling / roof
18,548BTU/h
Show the working
  1. 1. Wall: Q = A × ΔT ÷ R
    2,118 × 46 ÷ 4.24 = 22,978 BTU/h
  2. 2. Window: Q = A × ΔT ÷ R
    440 × 46 ÷ 1 = 20,240 BTU/h
  3. 3. Ceiling / roof: Q = A × ΔT ÷ R
    1,000 × 46 ÷ 2.48 = 18,548 BTU/h
  4. Air leakage: Q = 0.018 × volume × ΔT × ACH
    0.018 × 16,000 × 46 × 1.5 = 19,872 BTU/h

The component method

Heat flows through each part of the building envelope at a rate set by its area, its insulation and the temperature difference across it:

  • Conduction: Q = A × ΔT ÷ R, or A × U × ΔT, where U = 1 ÷ R.
  • Air leakage: Q = 0.018 × volume × ΔT × air changes per hour, where 0.018 BTU/ft³·°F is the heat needed to warm a cubic foot of air by one degree.

Add the components and the leakage to get the design heat loss: the heating capacity the building needs at the outdoor design temperature.

Checked against a published example

The example values the calculator opens with use the wall, ceiling and air-leakage figures from a Washington State energy factsheet on heat-loss calculation, archived by the Air Infiltration and Ventilation Centre. Its wall example (2,118 ft² of R-4.24 wall at a 46 °F difference loses 22,978 BTU/h) and its infiltration example (a 16,000 ft³ house at 1.5 air changes loses 19,872 BTU/h) are reproduced exactly by this engine in our automated tests.

Getting the R-values right

Use the whole-assembly R-value, not the insulation label. Wood studs, plates and headers bridge the insulation, so a wall’s overall R-value is lower than its cavity insulation’s. Windows and doors are rated by U-factor on their NFRC label; their R-value is 1 ÷ U. Basement walls and slabs lose heat to the ground rather than the outdoor air, and need a different method.

Worked example

These are the example values the calculator opens with, and the result the engine calculates for them.

Inputs

Indoor temperature
70 °F
Outdoor design temperature
24 °F
Number of components
3 components
Component 1: type
Wall
Component 1: area
2,118 ft²
Component 1: R-value (whole assembly)
4.24 h·ft²·°F/BTU
Component 2: type
Window
Component 2: area
440 ft²
Component 2: R-value (whole assembly)
1 h·ft²·°F/BTU
Component 3: type
Ceiling / roof
Component 3: area
1,000 ft²
Component 3: R-value (whole assembly)
2.48 h·ft²·°F/BTU
Heated volume (for air leakage)
16,000 ft³
Air changes per hour (natural)
1.5

Result

Total heat loss
81,639 BTU/h
Total heat loss
23.93 kW
Conduction (all components)
61,767 BTU/h
Air leakage
19,872 BTU/h
UA (conduction per °F)
1,343 BTU/h·°F

Total heat loss about 81,639 BTU/h (23.9 kW) at 46 °F temperature difference.

Assumptions

  • Steady-state conduction, Q = A × ΔT ÷ R, for each component; air leakage Q = 0.018 × volume × ΔT × ACH (0.018 BTU per ft³ per °F for air).
  • R-values are for the whole assembly, including framing and air films — usually lower than the insulation label. For a window or door use 1 ÷ its NFRC U-factor.

Limitations

  • Below-grade walls and slabs lose heat differently (to the ground); use a slab-edge or ground-coupled method for them.
  • This is a heat-loss calculation only; it does not include solar or internal gains.

Frequently asked questions

What is the difference between R-value and U-value?

R-value is resistance to heat flow; U-value is how easily heat flows. They are reciprocals: U = 1 ÷ R. A window with U-factor 0.30 has an R-value of about 3.3.

What outdoor design temperature should I use?

The 99 % heating design temperature for your location: the temperature the outdoor air stays above for all but about 88 hours of a typical year. ACCA Manual J and ASHRAE publish these by city.

How do I estimate air changes per hour?

A blower-door test is best: natural ACH is roughly ACH50 divided by an adjustment factor that depends on climate and building height. Without a test, about 0.3 is typical of a tight new home and 1.0 or more of a leaky older one.

Is heat loss the same as furnace size?

Heat loss is the output the building needs. A furnace’s input rating is higher by its efficiency: input = heat loss ÷ AFUE. The Furnace Sizing Calculator does that step.

Sources

  1. Calculating heat loss by infiltration (factsheet, 1988) — Washington Energy Extension Service (via AIVC). Infiltration heat loss Q = 0.018 × ACH × volume × ΔT.
  2. Heat Loss from Buildings — The Engineering ToolBox. Conduction heat loss Q = U·A·ΔT with U = 1/ΣR.