HVAC Load Calculator
Enter the building’s own numbers — R-values, window ratings, air leakage, design temperatures — and see the heating and cooling loads with a component-by-component breakdown.
Method reviewed October 22, 2026. Version 1.0.0. How it works
Result
- Total cooling load
- 27,395BTU/h
- Required capacity
- 2.28tons
- Design heat loss
- 42,487BTU/h
Design heat loss ≈ 42,487 BTU/h; cooling load ≈ 27,395 BTU/h (2.3 tons).
- Suggested nominal size
- 2.5tons
- Sensible load
- 24,691BTU/h
- Latent (moisture) load
- 2,704BTU/h
- Sensible heat ratio
- 0.9
- Floor area per ton
- 876ft²
Cooling load breakdown
- Walls
- 2,579BTU/h
- Ceiling / roof
- 3,067BTU/h
- Windows (conduction)
- 2,352BTU/h
- Windows (solar)
- 8,820BTU/h
- Doors
- 256BTU/h
- Air leakage (infiltration)
- 3,286BTU/h
- Occupants
- 1,720BTU/h
- Appliances & lighting
- 1,200BTU/h
- Duct losses / gains
- 4,115BTU/h
Heat loss breakdown
- Walls
- 5,555BTU/h
- Ceiling / roof
- 3,733BTU/h
- Windows (conduction)
- 8,232BTU/h
- Doors
- 896BTU/h
- Slab edge
- 7,313BTU/h
- Air leakage (infiltration)
- 9,677BTU/h
- Duct losses / gains
- 7,081BTU/h
Show the working
- Footprint and perimeter (square plan)2,000 ft² / 1 = 2,000 ft²; perimeter = 4 × √2,000 = 178.9 ft
- Net wall area1,431 ft² gross − 300 ft² windows − 40 ft² doors = 1,091 ft²
- Conditioned volume2,000 ft² × 8 ft = 16,000 ft³
- Cooling design temperature difference91 °F − 75 °F = 16 °F
- Total cooling load24,691 sensible + 2,704 latent = 27,395 BTU/h
- Convert to tons (12,000 BTU/h per ton)27,395 / 12,000 = 2.28 tons
- Heating design temperature difference70 °F − 14 °F = 56 °F
- Design heat loss including ducts42,487 BTU/h
Who this is for
It is the detailed version of the AC Tonnage and Furnace Sizing calculators: instead of picking “average insulation”, you enter the actual values. It suits energy auditors, designers, students and homeowners who have an energy-audit report or construction drawings to work from.
Method
Each part of the envelope is treated as a heat path:
- Conduction: Q = U × A × ΔT, where U = 1 ÷ R. Walls use an effective whole-wall R-value (lower than the insulation label, because studs bridge the insulation).
- Sun on opaque surfaces is approximated with a higher effective temperature difference: +10 °F for walls and +30 °F for a ceiling under a vented attic.
- Solar gain through glass: window area × SHGC × an average solar factor × an interior-shading factor.
- Air leakage: 1.08 × CFM × ΔT for temperature and 0.68 × CFM × Δgrains for moisture, with CFM from the air-change rate and house volume.
- Slab floors lose heat along their exposed edge: F-factor × perimeter × ΔT.
- People and appliances add internal heat in summer.
A duct allowance is added last as a percentage of the sensible load.
Using the breakdown
The breakdown shows where the load comes from. If windows dominate the cooling load, shading or a lower-SHGC window does more than added attic insulation. If air leakage dominates heating, air sealing is usually the cheapest improvement. Change one input at a time and watch which line moves.
Worked example
These are the example values the calculator opens with, and the result the engine calculates for them.
Inputs
- Conditioned floor area
- 2,000 ft²
- Stories above grade
- 1 story
- Average ceiling height
- 8 ft
- Outdoor cooling design temperature (1 %)
- 91 °F
- Outdoor heating design temperature (99 %)
- 14 °F
- Indoor cooling set point
- 75 °F
- Indoor heating set point
- 70 °F
- Design moisture difference (outdoor − indoor)
- 35 gr/lb
- Effective whole-wall R-value
- 11 h·ft²·°F/BTU
- Ceiling / attic R-value
- 30 h·ft²·°F/BTU
- Window area (% of floor area)
- 15 %
- Window U-factor
- 0.49 BTU/h·ft²·°F
- Window SHGC
- 0.7
- Exterior doors
- 2
- Natural air changes per hour (winter)
- 0.6
- Foundation
- Slab on grade
- Slab edge F-factor
- 0.73 BTU/h·ft·°F
- Duct loss / gain allowance
- 20 %
- Occupants
- 4
Result
- Total cooling load
- 27,395 BTU/h
- Required capacity
- 2.28 tons
- Suggested nominal size
- 2.5 tons
- Sensible load
- 24,691 BTU/h
- Latent (moisture) load
- 2,704 BTU/h
- Sensible heat ratio
- 0.9
Design heat loss ≈ 42,487 BTU/h; cooling load ≈ 27,395 BTU/h (2.3 tons).
Assumptions
- The house is modelled as a square footprint with two 20 ft² doors; homes with complex shapes have more wall area and a somewhat higher load.
- Opaque surfaces use an equivalent temperature difference for sun-heated surfaces: walls +10 °F, ceilings under a vented attic +30 °F.
- Window solar gain uses an all-orientation average of 60 BTU/h·ft² (calibrated so typical results fall in the range published Manual J studies report) multiplied by the window SHGC and an interior-shading factor of 0.7.
- Summer air leakage is taken as half of the winter natural air-change rate.
- Each occupant adds 230 BTU/h sensible and 200 BTU/h latent heat; appliances and lighting add 1,200 BTU/h.
Limitations
- This is a screening estimate, not an ACCA Manual J load calculation. Use it to sanity-check a quote or plan a project, not to finalise equipment selection.
- Orientation, shading by trees or neighbouring buildings, actual window placement, and room-by-room loads are not modelled; a whole-house figure cannot size individual duct runs.
- Conditioned basements are not modelled; below-grade wall losses are excluded.
Frequently asked questions
What design temperatures should I use?
The 99 % heating and 1 % cooling dry-bulb temperatures for the nearest weather station. Your local building department, an energy-code compliance document or your HVAC contractor’s Manual J report will list them. They are lower and higher than average weather — that is the point: equipment is sized for conditions exceeded only about 1 % of the year.
What is a whole-wall R-value?
The R-value of the wall assembly as built, including the framing that interrupts the insulation, plus sheathing, drywall and air films. A 2×4 wall with R-13 batts typically performs closer to R-10 or R-11 as a whole.
How do I find my air-change rate?
A blower-door test reports ACH50 (air changes at 50 pascals). Natural air changes are much lower; a common rough conversion divides ACH50 by a factor of about 10–20, depending on climate, building height and exposure. Without a test, use the guidance under the field.
Sources
- Manual J — Residential Load Calculation — Air Conditioning Contractors of America (ACCA). Manual J is the ANSI-recognised standard for residential equipment-sizing loads required by building codes.
- Manual J Load Calculations vs. Rules of Thumb — ACCA HVAC Blog (A. Bailes). Square feet per ton is not a sizing method; Manual J results commonly exceed 1,000 ft² per ton.
- Heat Loss from Buildings — The Engineering ToolBox. Conduction heat loss Q = U·A·ΔT with U = 1/ΣR.
- Calculating heat loss by infiltration (factsheet, 1988) — Washington Energy Extension Service (via AIVC). Infiltration heat loss Q = 0.018 × ACH × volume × ΔT.
- Regional Line Card — air-side formulas — Trane. Sensible = 1.08 × CFM × ΔT; latent = 0.68 × CFM × Δgr; total = 4.5 × CFM × Δh, with the derivation of each constant.
Spotted an error? Report a problem with this calculator — see our corrections policy.