Generator Sizing Estimator for HVAC Equipment
Will a generator run your house and start the air conditioner? Compare its running rating with your load, and its motor-starting capability with the compressor’s locked-rotor kVA.
Method reviewed October 26, 2026. Version 1.0.0. How it works
This is an estimate. It uses a simplified method and typical assumptions, all listed below. Use it to plan and to check quotes; equipment should be sized from a full room-by-room load calculation (ACCA Manual J) by a qualified professional.
Result
Looks adequate
- Largest motor starting kVA (full voltage)
- 19.68kVA
- Total running load
- 9,500W
Running 9,500 W (79 %); starting 19.7 kVA vs 20 kVA capability — looks adequate.
- Generator manufacturers note that motor starting depends on voltage dip, starting power factor and the alternator, and recommend their sizing software for a final selection. Treat this as a first check.
- Running load share of generator rating
- 79%
- Starting kVA share of generator capability
- 98%
- Starting kVA if voltage dips 30 %
- 9.64kVA
Show the working
- Starting kVA = LRA × V ÷ 1,00082 × 240 ÷ 1,000 = 19.68 kVA
- Running load = other loads + largest motor running6,000 + 3,500 = 9,500 W (79 % of 12,000 W)
- Starting kVA falls with the square of the voltage: at a 30 % dip, 0.7² = 0.4919.68 × 0.49 = 9.64 kVA
Running load and starting load
A generator has to carry everything that is already running and then survive the surge when the largest motor starts. For most homes that motor is the air conditioner or heat pump compressor.
Starting kVA at full voltage = locked-rotor amps × volts ÷ 1,000 (× 1.732 for three-phase). Kohler notes that starting current is typically about six times full-load current.
Why this is only a first check
When a motor starts on generator power, the voltage dips, and the starting kVA falls with the square of the voltage: a 30 % dip cuts it to 49 %. How deep a dip your equipment tolerates, the starting power factor and the alternator design all matter, which is why generator manufacturers provide their own sizing software.
Use this estimate to shortlist generator sizes, then confirm with the generator manufacturer. A soft starter on the compressor can lower the starting current substantially.
Worked example
These are the example values the calculator opens with, and the result the engine calculates for them.
Inputs
- Running load while the largest motor starts
- 6,000 W
- Running watts of the largest motor
- 3,500 W
- Locked-rotor amps (LRA) of the largest motor
- 82 A
- Motor voltage
- 240 V
- Supply
- Single-phase
- Generator continuous (running) rating
- 12,000 W
- Generator motor-starting capability
- 20 kVA
Result
- Largest motor starting kVA (full voltage)
- 19.68 kVA
- Total running load
- 9,500 W
- Running load share of generator rating
- 79 %
- Starting kVA share of generator capability
- 98 %
- Starting kVA if voltage dips 30 %
- 9.64 kVA
Running 9,500 W (79 %); starting 19.7 kVA vs 20 kVA capability — looks adequate.
Assumptions
- Only the largest motor starts while everything else is already running.
- Full-voltage starting kVA from the nameplate LRA; generator capabilities are entered from the manufacturer’s data.
Limitations
- Voltage dip, frequency dip and starting power factor are not modelled; manufacturers’ sizing software should be used for the final choice.
- A permanently connected generator needs a transfer switch installed by a licensed electrician; never back-feed a home through an outlet.
Frequently asked questions
Where do I find locked-rotor amps?
On the outdoor unit’s nameplate or the compressor label, marked LRA.
Can I plug a generator into an outlet to power the house?
No. Back-feeding is dangerous for you and for utility workers. A licensed electrician must install a transfer switch or interlock.
What generator rating should I compare with starting kVA?
The motor-starting kVA or surge rating from the generator manufacturer’s data, ideally at the voltage dip you can accept.
Sources
- Sizing Generators for Motor Starting: A Practical Guide (Power Systems Topics 103) — D. Krueger and R. Van Maaren, Kohler Power Systems. Starting current is typically six times full-load current; starting kVA falls as the square of the voltage dip (a 30 % dip reduces it to 49 %); motor interactions make manual generator sizing difficult, and manufacturers provide sizing software.
- University Physics Volume 2, §15.2 Simple AC Circuits — OpenStax, Rice University (CC BY 4.0). Capacitive reactance X_C = 1 ÷ (2π f C), so C = I ÷ (2π f V).
- Determining Electric Motor Load and Efficiency — U.S. DOE. Equation 1: three-phase input kW = V × I × PF × √3 ÷ 1,000 (worked example 469.7 V, 37 A, PF 0.763 → 22.9 kW); Equation 2: full-load input kW = hp × 0.7457 ÷ efficiency.
Spotted an error? Report a problem with this calculator — see our corrections policy.