Vacuum Decay Test, Micron and Absolute Pressure Calculator
Three tools in one: check whether an evacuated system held its vacuum, convert vacuum readings between units, and convert gauge to absolute pressure at your elevation.
Method reviewed October 26, 2026. Version 1.0.0. How it works
Result
Held
- Rise during the hold
- 120microns
- Average rate of rise
- 8microns/min
120 microns rise over 15 minutes — held.
- Rise per 10 minutes
- 80microns
- Final absolute pressure
- 56Pa
Show the working
- Rise = final − start420 − 300 = 120 microns
- Rate = rise ÷ hold time120 ÷ 15 min = 8 microns/min
- Checksfinal 420 ≤ 500: yes; rise 120 ≤ 200: yes
The decay (standing vacuum) test
After evacuating, the technician isolates the pump and watches the micron gauge. New York’s Clean Heat checklist evacuates to 500 microns or the manufacturer’s target, holds for at least 15 minutes, and calls for investigation if the reading rises by more than 200 microns.
A reading that keeps rising steadily suggests a leak. One that rises and then levels off suggests moisture or refrigerant still boiling off inside the system.
Microns, Torr and inches of mercury
A micron of mercury is a thousandth of a millimetre of mercury, or 0.001 Torr — about 0.133 Pa. Micron, Torr and pascal readings are absolute: zero is a perfect vacuum.
Inches of mercury vacuum on a compound gauge are measured down from the local atmosphere instead, so the same absolute pressure reads differently at different elevations. The converter uses the standard atmosphere at the elevation you enter.
Gauge and absolute pressure at altitude
Absolute pressure is gauge pressure plus the local atmospheric pressure, about 14.7 psia at sea level and 12.2 psia at 5,000 feet. Refrigerant property tables use absolute pressure, which is why altitude shifts the gauge reading for a given saturation temperature.
Worked example
These are the example values the calculator opens with, and the result the engine calculates for them.
Inputs
- Calculate
- Vacuum decay (standing) test
- Reading when the pump was isolated
- 300 microns
- Reading at the end of the hold
- 420 microns
- Hold time
- 15
- Highest acceptable final reading
- 500 microns
- Largest acceptable rise during the hold
- 200 microns
Result
- Rise during the hold
- 120 microns
- Average rate of rise
- 8 microns/min
- Rise per 10 minutes
- 80 microns
- Final absolute pressure
- 56 Pa
120 microns rise over 15 minutes — held.
Assumptions
- 1 micron of mercury = 0.001 Torr = 0.1333224 Pa; in. Hg is the conventional inch of mercury (3,386.389 Pa).
- Local atmospheric pressure from the standard atmosphere at the entered elevation (weather changes it by a few percent).
Limitations
- Micron gauges are most accurate near the bottom of their range; readings above a few thousand microns are approximate.
- Evacuation targets and hold times come from the equipment manufacturer. Only certified technicians may open refrigerant circuits (EPA Section 608).
Frequently asked questions
How many microns is a good vacuum?
Follow the manufacturer’s target. New York’s Clean Heat checklist uses 500 microns or the manufacturer’s target, held for at least 15 minutes.
How many Pa is 500 microns?
About 66.7 Pa, or 0.5 Torr.
Why does my compound gauge read less than 29.92 in. Hg at full vacuum?
At altitude the atmosphere is lower, so even a perfect vacuum reads less in inches of mercury below atmosphere.
Sources
- Recommended Air Source Heat Pump Commissioning Checklist — NYS Clean Heat Statewide Heat Pump Program (New York). Pressure test to the manufacturer’s specification and check the change against the allowable variance; evacuate to 500 microns or the manufacturer’s target, hold at least 15 minutes, and investigate if the vacuum rises by more than 200 microns.
- NIST Guide to the SI (SP 811), Appendix B.8 — factors for units listed alphabetically — National Institute of Standards and Technology. To pascals: inch of water, conventional 249.0889; inch of mercury, conventional 3,386.389; millimeter of mercury, conventional 133.3224; torr 133.3224; psi 6,894.757; bar 1 × 10⁵; millibar 100; standard atmosphere 101,325.
- PsychroLib — psychrometric functions after ASHRAE Handbook—Fundamentals (2017) ch. 1 — PsychroLib (open source, MIT licence). Humidity ratio W = 0.621945·pw/(p − pw), wet-bulb, enthalpy and standard-atmosphere equations as published by ASHRAE.
Spotted an error? Report a problem with this calculator — see our corrections policy.