Refrigerant Pressure–Temperature Calculator

Find the saturation pressure of R-410A, R-32, R-22 or R-134a at any temperature — or the saturation temperature behind a gauge reading — corrected for your elevation.

Method reviewed October 26, 2026. Version 1.0.0. How it works

Your inputs

Unit system

Only refrigerants whose generated tables agree with at least two independent published tables are offered. R-454B is not offered yet.

Gauges read pressure above the local atmosphere, which is lower at altitude. Leave at 0 for sea level.

Result

Dew-point pressure (gauge)
118.4psi
Bubble-point pressure (gauge)
118.8psi

R-410A at 40 °F: 118.4 psig dew point, 118.8 psig bubble point.

Temperature glide at the bubble-point pressure
0.19°F
Absolute pressure
133.1psia
Show the working
  1. Local atmospheric pressure (standard atmosphere)
    14.696 psia at 0 ft
  2. Dew-point and bubble-point pressures from the saturation table
    dew 133.1 psia, bubble 133.5 psia
  3. Gauge pressure = absolute − atmospheric
    133.1 − 14.696 = 118.4 psig

What a PT relationship tells you

While liquid and vapor refrigerant are both present — inside an evaporator or a condenser — pressure and temperature are locked together. Know one and you know the other. That is why a gauge reading can tell you the temperature at which the refrigerant is boiling in the indoor coil or condensing in the outdoor coil.

Once the refrigerant is all vapor (leaving the evaporator) or all liquid (leaving the condenser), the link breaks: its temperature can rise above or fall below the saturation temperature. Those differences are superheat and subcooling.

Dew point, bubble point and glide

A single-component refrigerant such as R-32, R-22 or R-134a boils and condenses at one temperature for a given pressure. A blend boils over a small range: the bubble point is where the first vapor appears in the liquid, and the dew point is where the last liquid disappears. The difference is the temperature glide.

R-410A is a near-azeotropic blend with a glide of only about 0.2 °F, so in practice it behaves almost like a single refrigerant. The calculator still shows both values, because superheat should be measured from the dew point and subcooling from the bubble point.

Gauge pressure and altitude

Refrigerant properties depend on absolute pressure, but a gauge reads pressure above the surrounding air. At sea level the air is about 14.7 psi; at 5,000 feet it is about 12.2 psi. So at altitude the same refrigerant temperature shows a gauge reading roughly 2.5 psi higher. Printed PT charts assume sea level; enter your elevation here to correct for it.

Where the numbers come from

The saturation tables are computed with CoolProp, an open-source property library, and checked against independent published tables before a refrigerant is offered. The Refrigerant PT charts page lists every comparison and explains why R-454B is not offered yet.

Worked example

These are the example values the calculator opens with, and the result the engine calculates for them.

Inputs

Refrigerant
R-410A
I know the
Temperature — find the pressure
Saturation temperature
40 °F
Site elevation
0 ft

Result

Dew-point pressure (gauge)
118.4 psi
Bubble-point pressure (gauge)
118.8 psi
Temperature glide at the bubble-point pressure
0.19 °F
Absolute pressure
133.1 psia

R-410A at 40 °F: 118.4 psig dew point, 118.8 psig bubble point.

Assumptions

  • Saturation tables generated with CoolProp 8.0.0 every 1 °F and interpolated linearly; each refrigerant agrees with at least two independent published tables (see the validation report).
  • Gauge pressure = absolute pressure − local atmospheric pressure from the standard atmosphere at the site elevation.
  • For a blend, the dew point applies to saturated vapor (evaporator outlet, superheat) and the bubble point to saturated liquid (condenser outlet, subcooling).

Limitations

  • Gauge accuracy, weather-related changes in barometric pressure and non-condensable gases all affect field readings.
  • Use the equipment manufacturer’s charging chart and procedure; this tool gives saturation properties only.

Frequently asked questions

What pressure should R-410A be at 40 °F?

About 118 psig at sea level for the dew point (vapor), and about 119 psig for the bubble point (liquid). At higher elevations the gauge reading is a little higher.

Why does my gauge show a slightly different number than a printed chart?

Printed charts assume sea-level air pressure and usually round to whole degrees or whole psi. Gauge accuracy, today’s barometric pressure and non-condensable gases in the system also shift readings.

Can I use this to charge a system?

It gives saturation temperatures, which are one input to charging. The charging method, the target superheat or subcooling and the tolerance come from the equipment manufacturer.

Why is R-454B not available?

The open-source model we use differs from two independent published R-454B tables by about 1 °F, which is too much for charging work. We will add it once a model or dataset agrees with independent sources.

Sources

  1. CoolProp — open-source thermophysical property library (version 8.0.0) — CoolProp developers (MIT licence). Equations of state for pure fluids and mixtures, incompressible fluids and brines, and IAPWS-IF97 water/steam; free for commercial use under its licence. Used here to generate the refrigerant saturation tables.
  2. Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp — Bell, Wronski, Quoilin & Lemort, Industrial & Engineering Chemistry Research 53(6), 2498–2508 (2014), open access. The citation CoolProp asks users to give; describes the equations of state and their accuracy.
  3. Refrigerant PT charts and how they were validated — FreeHVACCalculators.com. Each published refrigerant’s generated table agrees with at least two independent published tables (worst differences and tolerances listed); R-454B is withheld because it does not.
  4. NIST Guide to the SI (SP 811), Appendix B.9 — conversion factors — National Institute of Standards and Technology. 1 ton of refrigeration = 12,000 BTU/h; 1 BTU/h = 0.2930711 W; 1 atm = 101.325 kPa.

Spotted an error? Report a problem with this calculator — see our corrections policy.