Electric Baseboard and Space Heater Sizing Calculator

Electric resistance heat turns every watt into 3.412 BTU/h. Find the room’s heat loss and the heater wattage that replaces it.

Method reviewed October 26, 2026. Version 1.0.0. How it works

This is an estimate. It uses a simplified method and typical assumptions, all listed below. Use it to plan and to check quotes; equipment should be sized from a full room-by-room load calculation (ACCA Manual J) by a qualified professional.

Your inputs

Unit system

Length of walls facing outdoors (0 for an interior room).

Roof or attic above?
Heater voltage

Result

Heater wattage needed
1,110W
Current at 240 V
4.62A

About 1,110 W of electric heat (4.6 A at 240 V) replaces the 3,787 BTU/h the room loses at design conditions.

  • Heaters come in fixed sizes; choose the nearest size at or above this figure. Circuit, wire and breaker sizing follow the heater’s instructions and the electrical code — have a licensed electrician install hard-wired heaters.
Heater size
1.11kW
Room heat loss
3,787BTU/h
Show the working
  1. Design conditions
    70 °F inside, 0 °F outside (ΔT 70 °F); walls R-11, ceiling R-30, windows U-0.49, 0.6 air changes per hour
  2. Room heat loss (walls, windows, ceiling, floor and air leakage; no ducts)
    3,787 BTU/h
  3. Watts = BTU/h ÷ 3.412
    3,787 ÷ 3.412 = 1,110 W
  4. Current = watts ÷ volts
    1,110 ÷ 240 = 4.6 A

From heat loss to watts

Electric baseboard heaters, wall heaters and plug-in space heaters convert all of their electricity to heat, so the conversion is exact: watts = BTU/h ÷ 3.412. The current is watts ÷ volts.

If you know the room’s design heat loss from a load calculation, enter it directly. Otherwise the tool estimates it from the room’s floor area, exterior wall length, windows, what is above and below, a preset insulation level and your climate — the same component method as our Room-by-Room Load Estimator, without duct losses.

Choosing heaters

Heaters come in fixed sizes, so choose the nearest size at or above the result — or split it between two heaters on long outside walls or under windows. Plug-in space heaters are limited by the outlet circuit they share with other loads; larger rooms usually need hard-wired 240 V heat or several heaters on separate circuits.

Wire size, breaker size and the number of heaters per circuit follow the heater’s instructions and the electrical code. Have a licensed electrician install hard-wired heaters.

Worked example

These are the example values the calculator opens with, and the result the engine calculates for them.

Inputs

Start from
Room details (estimate the heat loss)
Climate
Zone 5 — cool (e.g. Chicago)
Room floor area
200 ft²
Ceiling height
8 ft
Exterior wall length
25 ft
Window area
30 ft²
Roof or attic above?
Yes (top floor)
Floor
Over heated space
Insulation & air sealing
Average (code-built 1990s–2000s)
Window type
Double pane, clear
Heater voltage
240 V

Result

Heater wattage needed
1,110 W
Heater size
1.11 kW
Current at 240 V
4.62 A
Room heat loss
3,787 BTU/h

About 1,110 W of electric heat (4.6 A at 240 V) replaces the 3,787 BTU/h the room loses at design conditions.

Assumptions

  • Electric resistance heat turns 100 % of its electricity into heat: watts = BTU/h ÷ 3.412.
  • Room estimates use the same component method as the Room-by-Room Load Estimator, with 70 °F inside and no duct losses (baseboard heat has no ducts).

Limitations

  • Room estimates rely on preset insulation, window and air-leakage levels; enter a calculated heat loss for a better answer.
  • No allowance is added for fast warm-up after a setback.

Frequently asked questions

How many watts per square foot for baseboard heat?

There is no fixed figure: a well-insulated room in a mild climate may need a few watts per square foot, a drafty room with large windows in a cold climate several times more. The room estimate shows why.

Does a 240 V heater use less electricity than a 120 V one?

No. For the same wattage, the energy and the heat are identical; a 240 V heater simply draws half the current.

Is electric resistance heat 100 % efficient?

At the heater, yes — all the electricity becomes heat. A heat pump delivers more heat per kWh, which is why it usually costs less to run.

Sources

  1. NIST Guide to the SI (SP 811), Appendix B.9 — conversion factors — National Institute of Standards and Technology. 1 ton of refrigeration = 12,000 BTU/h; 1 BTU/h = 0.2930711 W; 1 atm = 101.325 kPa.
  2. University Physics Volume 2, §9.4 Ohm’s Law — OpenStax, Rice University (CC BY 4.0). V = IR; electrical power P = IV.
  3. Heat Loss from Buildings — The Engineering ToolBox. Conduction heat loss Q = U·A·ΔT with U = 1/ΣR.
  4. Calculating heat loss by infiltration (factsheet, 1988) — Washington Energy Extension Service (via AIVC). Infiltration heat loss Q = 0.018 × ACH × volume × ΔT.