South Dakota design temperatures

Outdoor heating and cooling design conditions for 6 South Dakota weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for South Dakota weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
AberdeenWMO 726590 · 1973–19961,299 ft−19 °F−14 °F91 / 71 °F95 / 72 °FLoad calculator
Ellsworth AFBWMO 726625 · 1967–19963,278 ft−10 °F−5 °F92 / 65 °F96 / 66 °FLoad calculator
HuronWMO 726540 · 1973–19961,289 ft−16 °F−12 °F92 / 72 °F95 / 73 °FLoad calculator
PierreWMO 726686 · 1973–19961,742 ft−14 °F−8 °F95 / 70 °F99 / 70 °FLoad calculator
Rapid CityWMO 726620 · 1973–19963,169 ft−11 °F−6 °F92 / 65 °F96 / 66 °FLoad calculator
Sioux FallsWMO 726510 · 1973–19961,427 ft−16 °F−11 °F91 / 73 °F94 / 73 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states