New Hampshire design temperatures

Outdoor heating and cooling design conditions for 4 New Hampshire weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for New Hampshire weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
ConcordWMO 726050 · 1973–1996345 ft−8 °F−2 °F87 / 70 °F90 / 72 °FLoad calculator
LebanonWMO 726116 · 1973–1996597 ft−10 °F−4 °F86 / 70 °F89 / 71 °FLoad calculator
ManchesterWMO 743945 · 1973–1996233 ft1 °F6 °F90 / 72 °F92 / 73 °FLoad calculator
Pease AFB/PortsmouthWMO 726055 · 1967–1996102 ft2 °F6 °F85 / 71 °F88 / 73 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states