Mississippi design temperatures

Outdoor heating and cooling design conditions for 6 Mississippi weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Mississippi weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Columbus AFBWMO 723306 · 1967–1996220 ft20 °F24 °F94 / 77 °F96 / 77 °FLoad calculator
Jackson/ThompsonWMO 722350 · 1973–1996331 ft21 °F25 °F94 / 77 °F96 / 77 °FLoad calculator
Keesler AFB/BiloxiWMO 747686 · 1967–199633 ft30 °F34 °F92 / 79 °F93 / 79 °FLoad calculator
McComb/LewisWMO 722358 · 1973–1996413 ft23 °F27 °F92 / 76 °F94 / 76 °FLoad calculator
Meridian NAS/McCainWMO 722345 · 1973–1996318 ft20 °F24 °F94 / 77 °F97 / 77 °FLoad calculator
Meridian/KeyWMO 722340 · 1973–1996308 ft21 °F25 °F94 / 76 °F96 / 77 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states