Utah design temperatures

Outdoor heating and cooling design conditions for 5 Utah weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Utah weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Cedar CityWMO 724755 · 1973–19965,624 ft4 °F9 °F92 / 59 °F94 / 59 °FLoad calculator
Hill AFB/OgdenWMO 725755 · 1967–19964,787 ft7 °F12 °F91 / 61 °F93 / 61 °FLoad calculator
ProvoWMO 725724 · 1980–19964,492 ft4 °F10 °F92 / 63 °F95 / 64 °FLoad calculator
Salt Lake CityWMO 725720 · 1973–19964,226 ft7 °F12 °F95 / 63 °F97 / 63 °FLoad calculator
WendoverWMO 725810 · 1973–19954,239 ft4 °F11 °F94 / 60 °F97 / 61 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.