Oklahoma design temperatures

Outdoor heating and cooling design conditions for 7 Oklahoma weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Oklahoma weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Altus AFBWMO 723520 · 1967–19961,378 ft14 °F19 °F100 / 73 °F102 / 73 °FLoad calculator
Fort SillWMO 723550 · 1967–19961,188 ft14 °F19 °F98 / 74 °F101 / 73 °FLoad calculator
Mc AlesterWMO 723566 · 1973–1996771 ft11 °F17 °F96 / 76 °F98 / 76 °FLoad calculator
Oklahoma CityWMO 723530 · 1973–19961,303 ft9 °F15 °F96 / 74 °F99 / 74 °FLoad calculator
Tinker AFBWMO 723540 · 1967–19961,293 ft11 °F17 °F96 / 74 °F98 / 75 °FLoad calculator
Tulsa (Aw)WMO 723560 · 1973–1996676 ft9 °F14 °F97 / 76 °F100 / 76 °FLoad calculator
Vance AFB/EnidWMO 723535 · 1967–19961,306 ft8 °F14 °F98 / 73 °F101 / 74 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states