Missouri design temperatures

Outdoor heating and cooling design conditions for 8 Missouri weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Missouri weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
ColumbiaWMO 724450 · 1973–1996899 ft−1 °F5 °F92 / 76 °F95 / 76 °FLoad calculator
Fort Leonard WoodWMO 724457 · 1967–19961,158 ft5 °F11 °F93 / 75 °F96 / 76 °FLoad calculator
JoplinWMO 723495 · 1973–1996981 ft4 °F10 °F94 / 75 °F96 / 75 °FLoad calculator
Richards-Gebaur AFBWMO 724466 · 1967–19961,093 ft1 °F7 °F94 / 75 °F97 / 75 °FLoad calculator
Spirit Of St LouisWMO 724345 · 1973–1996463 ft4 °F10 °F93 / 76 °F95 / 77 °FLoad calculator
SpringfldWMO 724400 · 1973–19961,270 ft2 °F9 °F92 / 75 °F95 / 74 °FLoad calculator
St. Louis/LambertWMO 724340 · 1973–1996564 ft1 °F8 °F93 / 76 °F96 / 77 °FLoad calculator
Whiteman AFBWMO 724467 · 1967–1996869 ft1 °F7 °F93 / 76 °F96 / 76 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states