Kentucky design temperatures

Outdoor heating and cooling design conditions for 5 Kentucky weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Kentucky weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Cincinnati/CovingtonWMO 724210 · 1973–1996876 ft0 °F7 °F89 / 74 °F91 / 75 °FLoad calculator
Fort Campbell (AAF)WMO 746710 · 1967–1996571 ft8 °F14 °F92 / 76 °F94 / 77 °FLoad calculator
Fort Knox/GodmanWMO 724240 · 1967–1996755 ft5 °F12 °F90 / 75 °F92 / 76 °FLoad calculator
Lexington/BluegrassWMO 724220 · 1973–1996988 ft4 °F10 °F89 / 74 °F91 / 75 °FLoad calculator
Louisville/StandifordWMO 724230 · 1973–1996489 ft6 °F12 °F91 / 76 °F93 / 77 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.