Indiana design temperatures

Outdoor heating and cooling design conditions for 6 Indiana weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Indiana weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
EvansvilleWMO 724320 · 1973–1996387 ft3 °F9 °F92 / 76 °F94 / 77 °FLoad calculator
Fort Wayne/BaerWMO 725330 · 1973–1996827 ft−4 °F1 °F88 / 73 °F91 / 74 °FLoad calculator
Grissom AFB/PeruWMO 725335 · 1967–1996810 ft−3 °F3 °F89 / 75 °F91 / 76 °FLoad calculator
IndianapolisWMO 724380 · 1973–1996807 ft−3 °F3 °F89 / 75 °F91 / 76 °FLoad calculator
South Bend/St. JosephWMO 725350 · 1973–1996774 ft−2 °F3 °F88 / 73 °F91 / 74 °FLoad calculator
Terre Haute/Hulman FieldWMO 724373 · 1973–1996584 ft−3 °F3 °F90 / 76 °F92 / 77 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.