Indiana design temperatures
Outdoor heating and cooling design conditions for 6 Indiana weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.
| Station | Elevation | 99.6 % heating | 99 % heating | 1 % cooling / MCWB | 0.4 % cooling / MCWB | Use it |
|---|---|---|---|---|---|---|
| EvansvilleWMO 724320 · 1973–1996 | 387 ft | 3 °F | 9 °F | 92 / 76 °F | 94 / 77 °F | Load calculator |
| Fort Wayne/BaerWMO 725330 · 1973–1996 | 827 ft | −4 °F | 1 °F | 88 / 73 °F | 91 / 74 °F | Load calculator |
| Grissom AFB/PeruWMO 725335 · 1967–1996 | 810 ft | −3 °F | 3 °F | 89 / 75 °F | 91 / 76 °F | Load calculator |
| IndianapolisWMO 724380 · 1973–1996 | 807 ft | −3 °F | 3 °F | 89 / 75 °F | 91 / 76 °F | Load calculator |
| South Bend/St. JosephWMO 725350 · 1973–1996 | 774 ft | −2 °F | 3 °F | 88 / 73 °F | 91 / 74 °F | Load calculator |
| Terre Haute/Hulman FieldWMO 724373 · 1973–1996 | 584 ft | −3 °F | 3 °F | 90 / 76 °F | 92 / 77 °F | Load calculator |
Using these values
- Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
- “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
- Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.