Arkansas design temperatures

Outdoor heating and cooling design conditions for 8 Arkansas weather stations. Choose the station nearest to you in distance and elevation, and check whether your building department specifies its own values.

Design temperatures for Arkansas weather stations, in degrees Fahrenheit
StationElevation99.6 % heating99 % heating1 % cooling / MCWB0.4 % cooling / MCWBUse it
Eaker AFBWMO 723408 · 1963–1992256 ft12 °F17 °F94 / 77 °F96 / 78 °FLoad calculator
El Dorado/GoodwinWMO 723419 · 1973–1996253 ft19 °F23 °F95 / 77 °F97 / 77 °FLoad calculator
Fayetteville/DrakeWMO 723445 · 1973–19961,250 ft7 °F12 °F92 / 75 °F95 / 75 °FLoad calculator
Fort SmithWMO 723440 · 1973–1996463 ft13 °F18 °F96 / 76 °F98 / 76 °FLoad calculator
Harrison/BooneWMO 723446 · 1973–19961,365 ft7 °F12 °F92 / 75 °F94 / 75 °FLoad calculator
Little Rock AFBWMO 723405 · 1967–1996312 ft16 °F21 °F95 / 77 °F98 / 78 °FLoad calculator
Pine Bluff/GriderWMO 723417 · 1973–1996207 ft19 °F23 °F95 / 77 °F97 / 78 °FLoad calculator
Texarkana/WebbWMO 723418 · 1973–1996390 ft20 °F25 °F95 / 77 °F98 / 77 °FLoad calculator

Using these values

  • Heat-loss calculations for homes commonly use the 99 % heating value, and cooling loads the 1 % dry bulb with its mean coincident wet bulb (MCWB). The 99.6 % and 0.4 % values are more conservative.
  • “Load calculator” opens the heating and cooling load calculator with that station’s 99 % and 1 % temperatures and its design moisture difference (outdoor air at the 1 % condition versus 75 °F, 50 % RH indoors, at the station’s elevation).
  • Source: U.S. Air Force Combat Climatology Center and NOAA National Climatic Data Center, Engineering Weather Data (1999; public domain). Each station’s period of record is shown under its name; they end by 1996, and the climate has warmed since, so check local requirements before relying on a value for a permit.

All states